ENGLISH ITALIANO РУССКИЙ
Skema - MV & LV Switchgear
 
Products and systems
Low Voltage
- PC 2000
- Intelligent MCC 2000
- MCC-F2000
Medium Voltage
MV/LV Substations
Local Equipments Rooms
IPCS
Support Services
 
Intelligent MCC 2000
 
 
 
 
 

 
Main characteristics

Rated insulation voltage (Ui)     1000V
  Rated operating voltage (Ue)     Up to 690 V
  Rated Frequency     50/60 Hz
Rated current main busbars   630 ÷ 4000 A
distribution busbars 630÷1250 A
Rated short - time withstand current for 1 sec. (Icw)
    40/50/70/80/100 kA
  Rated peak withstand current (Ipk)     84/105/154/176 kA
Degree of protection
(according to EN 60529)
external enclosure IP31/ IP42
     
with open door   IP2X/ IP4X
Maximum number of modules for section
    12 (24)
Size of withdrawable unit     1/2 - 1 - 1 1/2 - 2 - 3 - 4
Rated current clamps on withdrawable unit     = 400 A
  Rated current of auxiliary connector on withdrawable unit     10 A
  Standard colour of external enclosure     RAL 7032 other colours on request
  Access     from the front
  Installation     against a wall or back to back
  Entry and exit of cables     from top or bottom
  Dimensions of a section width  
800 mm
  height   2365 mm
  depth
  590 mm (2500 A)
840 mm (4000 A)